- 72 -
F2.08
Motor stator inductance Factory Setting Defined by inverter model
Setting Options
0.1~6553mH
F2.09
Motor rotator mutual
inductance
Factory Setting Defined by inverter model
Setting Range
0.1~6553mH
F2.10
Motor no-load current Factory Setting Defined by inverter model
Setting Range
0.1~655.3A
After automatic tuning of electric motor finished normally, the setting values of
F2.06~F2.10 will update automatically.
Every time after changing the rated power of F2.01, the VFD will restore the
standard default parameters of F2.06~F2.10.(Quadru-pole Y series asynchronous
motor)
If the spot situation do not allow tuning for electric motor, it is possible to refer to the
known parameters of the electric motors of same type and input the parameters
manually.
F2.11~F2.12 Reserved