35SALMSON 08/2016
100%
Set value 4-20mA
0 2 4
20
Input current (mA)
Set value
in % of the range
of measurement of
the sensor
Area where converter stops
Safety
area
100%
Set value 0-10V
0 1 2
10
Input voltage (V)
Set value
in % of the range
of measurement of
the sensor
Area where converter stops
Safety
area
IN2 : Entrée de la consigne externe en mode « Pression constante » et « Contrôle P.I.D. »
IN2 : Input of external frequency control in « Speed control » mode
100%
~30%
~30%
External Signal 0-20mA
0 2 4
6 10
20
Input current (mA)
Frequency of
the converter
Area where converter stops
Safety
area
100%
External Signal 4-20mA
0
20
Input current (mA)
Frequency of
the converter
Area where converter stops
Safety
area
~30%
3 5
100%
External Signal 2-10V
0
10
Input voltage (V)
Frequency of the
converter
Area where converter stops
Safety
area
100%
~30%
External Signal 0-10V
0 1 2
10
Input voltage (V)
Frequency of
the converter
Area where converter stops
Safety
area
English