12 | SAMLEX AMERICA INC. SAMLEX AMERICA INC. | 13
APPENDIX A
SECTION 4 | Parameter Setup
4.1 PARAMETER SETUP MENU MAPS
NOTES: Please refer to Page 13.
Fig 4.1 Parameter Setup Menu Map – Groups 1 to 4
Page 1
Group 1
SELECT GROUP
“CHARGE CURVE”
Group 2
SELECT GROUP
“INPUT SETTING”
Group 3
SELECT GROUP
“INPUT LOW LIMIT”
Group 4
SELECT GROUP
“INPUT HIGH LIMIT
BULK CURRENT
40 A
DEFAULT FREQ
0= 60 Hz
RESET VOLTAGE
135.0 V
RESET VOLTAGE
95.0 V
RESET VOLTAGE
14.00 V
DETECT TIME 3
1 cycle
LOW VOLT ALARM
11.00 V
BATT LOW VOLTAGE
10.50 V
LV DETECT TIME
10 sec
LV CUT OFF TIME
1200 sec
CHARGE MODE
0=Normal
ONLINE MODE
0=Off
Page 2
ABSORP VOLTAGE
14.40 V
GRID MAX CURRENT
30.00 A
CUT OFF VOLT 1
140.0 V
CUT OFF VOLT 1
90.0 V
Page 3
EQUALIZE VOLTAGE
14.40 V
GEN MAX CURRENT
30.00 A
DETECT TIME 1
60 cycles
DETECT TIME 1
300 cycles
Page 4
FLOATING VOLTAGE
13.50 V
HIGH CUT OFF
65.00 Hz
CUT OFF VOLT 2
85.0 V
Page 5
COMPENSATE
4 MV/C/C
LOW CUT OFF
55.00 Hz
DETECT TIME 2
60 cycles
Page 6
Page 7
Page 8
Page 9
Page 10
Page 11
Page 12
Page 13
Page 14
BATT OVER VOLT
16.00 V
LOW RESET
56.00 Hz
CUT OFF VOLT 3
80.0 V
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
HIGH RESET
64.00 Hz
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
òò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
ONLINE OPTIONS
0 = Option 1
ò
ò
ò
ò
ò
ò
ò
ò
ò
ò
DETECT TIME 3
1 cycle
CUT OFF VOLT 2
145.0 V
DETECT TIME 2
15 cycles
CUT OFF VOLT 3
150.0 V
ò
ò
ò
ò
ò
ò
ò
ò
Enter Key (To Group towards the right)
Back Key (To Group towards the left)
ò
ò
Page Up (Up Key)*
Page Down (Down Key)**
ò
ò
Page 15
FLOATING EXIT
12.00 V
ò
ò
Page 16
GS DETECT TIME
10 sec
ò
ò
Page 17
GEN ON TIME
60 min
ò
ò
Page 18
GEN OFF TIME
60 min
ò
ò