EB 3136 EN 23
Malfunctions
Table4: Troubleshooting
Malfunction Possible reasons Recommended action
Flow rate exceeds adjusted set
point
Leak between seat and plug
Remove valve from the pipeline
and clean seat and plug. Con-
tact SAMSON for further action.
Defective operating diaphragm
Contact SAMSON's After-sales
Service department.
Control line with needle valve
blocked.
Remove control line and needle
valve. Clean them.
Valve too large for control task
(ow rate) or too small
(differential pressure)
Recalculate K
VS
and contact
SAMSON for further action.
Flow set point not reached.
Leak between seat and plug
Remove valve from the pipeline
and clean seat and plug. Con-
tact SAMSON for further action.
Incorrect set point range
selected.
Check set point range and con-
tact SAMSON for further action.
Safety device, e.g. pressure
limiter, has been triggered.
Check plant. Unlock safety de-
vice.
Plant differential pressure too
low.
Compare differential pressure in
the plant with the plants drag.
Strainer blocked
Drain and clean lter of the
strainer.
Incorrectly installed valve
(direction of ow).
Install the regulator so that the
direction of ow matches the di-
rection indicated by the arrow
on the body.
Control loop hunts. Valve too large for control task
Recalculate K
VS
and contact
SAMSON for further action.
Contact SAMSON's After-sales Service department for malfunctions not listed in the table
and when the malfunction cannot be remedied as described.