What to do if there is increased flow through closed Samson Control Unit valve?
- JJanet ShepherdJul 27, 2025
If you observe increased flow through a closed Samson Control Unit valve, and suspect seat leakage, it might be due to dirt or foreign particles lodged between the seat and plug. In this case, shut off the pipeline section and flush the valve to remove any debris. Another potential cause is worn valve trim, especially with a soft seat. If this is the case, replace the seat and plug.