EasyManua.ls Logo

Samson 3510 - 5.3 Quick Check

Samson 3510
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 EB 8091-1 EN
Mounting and start-up
3. Lift the valve to the site of installation.
Observe the ow direction through the
valve. The arrow on the valve indicates
the direction of ow.
4. Make sure that the correct gaskets are
used on the end connections.
5. Bolt the pipe to the valve free of stress.
6. Depending on the eld of application,
allow the valve to cool down or heat up
to reach ambient temperature before
start up.
7. Slowly open the shut-off valve in the
pipeline after the valve has been in-
stalled.
Risk of valve damage due to a sudden pres-
sure increase and resulting high ow veloci-
ties.
Slowly open the shut-off valve in the pipeline
during start-up.
8. Check the valve to ensure it functions
properly.
Version with welding ends
1. Proceed as described for Version with
female thread or anges (steps 1 to 3).
2. Completely retract the actuator stem to
protect the plug from sparks during weld-
ing.
3. Weld the valve free of stress into the
pipeline.
4. Proceed as described for Version with fe-
male thread or anges (steps 6 to 8).
5.3 Quick check
SAMSON valves are delivered ready for
use. To test the valve's ability to function, the
following quick checks can be performed:
Tight shut-off
1. Close the valve.
2. Slowly open the shut-off valve in the
pipeline.
Risk of valve damage due to a sudden pres-
sure increase and resulting high ow veloci-
ties.
Slowly open the shut-off valve in the pipeline
during start-up.
3. Check the valve for leakage (visual in-
spection).
Travel motion
The movement of the actuator stem must be
linear and smooth.
Î Open and close the valve, observing the
movement of the actuator stem.
Î Apply the maximum and minimum con-
trol signals to check the end positions of
the valve.
Î Check the travel reading at the travel in-
dicator scale.
Fail-safe position
Î Shut off the signal pressure line.
Î Check whether the valve moves to the
fail-safe position.
NOTICE
!
NOTICE
!

Related product manuals