EasyManua.ls Logo

Samson 3730-3 - Readings; Operating Modes; Bar Graph; Status Messages

Samson 3730-3
180 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8384-3 EN 91
Operation
Readings
Icons assigned to certain codes, parameters
and functions are indicated on the display.
Operating modes:
(manual mode)
The positioner follows the manual set
point(Code1)insteadofthemAsignal.
blinks: The positioner is not initialized.
Operation only possible over manual set
point (Code 1).
(automatic mode)
The positioner is in closed-loop operation
and follows the mA signal.
S SAFE
The positioner vents the output. The valve
moves to the mechanical fail-safe posi-
tion.
Bar graph:
In manual
and automatic modes, the
bars indicate the set point deviation that de-
pendsonthesign(+/–)andthevalue.One
barelementappearsper1%setpointdevi-
ation.
If the positioner has not been initialized, (
blinks on the display), the bar graph indi-
cates the lever position in degrees in relation
to the mid-axis. One bar element corre-
sponds to approximately a 5° angle of rota-
tion.Thefthbarelementblinks(reading>
30°) if the permissible angle of rotation has
been exceeded. Lever and pin position must
be checked.
Status messages
Maintenance alarm
Maintenancedemanded/Mainte-
nance required
blinks:Outofspecication
These icons indicate that an error has oc-
curred.
Aclassiedstatuscanbeassignedtoeach
error.Classicationsinclude“Nomessage”,
“Maintenancerequired”,“Maintenancede-
manded”and“Maintenancealarm“(see
uEB8389onEXPERTplusvalvediagnos-
tics).
Enable conguration
This indicates that the codes marked with an
asterisk (*) in the code list are enabled for
conguration(seesection11.4).
6.1 Serial interface
The positioner must be supplied with at least
4mA.
The positioner can be connected directly to
the computer over the local serial interface
and the serial interface adapter.
TheoperatorsoftwareisTROVIS-VIEWwith
installed device module 3730-3.