Installation Procedure
34
English
Installation manual
CAUTION
Must fit tightly against body without any gap.
Make sure that all refrigerant connection must be
accessible for easy maintenance and detachment.
Install the insulation not to get wider and use the
adhesives on the connection part of it to prevent
moisture from entering.
Wind the refrigerant pipe with insulation tape if it is
exposed to outside sunlight.
Install the refrigerant pipe respecting that the insulation
does not get thinner on the bent part or hanger of pipe.
Add the additional insulation if the insulation plate gets
thinner.
All refrigerant connection must be accessible, in order
to permit eithernit maintenance or removal.
Additional insulation
Hanger
Refrigerant pipe insulation
a
a x 3
5 Select the insulation of the refrigerant pipe.
Insulate the gas side and liquid side pipe, noting the
insulation thickness that must differ according to
the pipe size.
Standard: Less than an indoor temperature of 30°C,
with humidity at 85%. If installing in a high humidity
environment, use one grade thicker insulator by
referring to the table below. If installing in an
unfavourable environment, use thicker one.
The heat-resistance temperature of the insulator
must be more than 120°C.
Pipe
Pipe size
(mm)
Insulation Type
(Heating/Cooling)
Remarks
Standard
[30°C,
85%]
High
humidity
[30°C,
over 85%]
EPDM, NBR
Liquid pipe
Ø6.35 to
Ø9.52
9t
Internal
temperature
is higher than
120°C
Ø12.7 to
Ø50.80
13t
Gas pipe
Ø6.35 13t 19t
Ø9.52 to
Ø25.40
19t
25t
Ø28.58 to
Ø44.45
32t
Ø50.80 25t 38t
When installing insulation in the places and
conditions below, use the same insulation that is
used for high humidity conditions.
<Geological condition>
High humidity locations such as shorelines, hot springs, lake
or riversides, and ridges (when part of the building is covered
by earth and sand)
<Operation purpose condition>
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
Ceilings frequently exposed to moisture and cooling are
not covered. For example, pipes installed at a corridor of a
dormitory and studio or near an exit that opens and closes
frequently.
Places (where the pipes are installed) that are highly humid
due to a lack of ventilation.
Refrigerant pipe before EEV kit and MCU or without
EEV kit and MCU
You can contact the gas side and liquid side
pipes but the pipes should not be pressed.
When contacting the gas side and liquid side
pipe, use 1 grade thicker insulator.