Loading...
Setting indoor unit addresses and installation option
68
English
Installation manual
Changing the addresses and options individually
When you want to change the value of a specific option, refer to the following table and follow the steps in Common steps for
setting the addresses and options on page 51.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Function Page Mode
Type of the option to
change
Tens position of the
option number
Units position of the
option number
New value
Indication and
details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 D Option type 0 to F
Tens
position
value
0 to 9
Units
position
value
0 to 9 New value 0 to F
Example: Changing the Buzzer control (SEG17) option of the installation options to 1 disuse.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Function Page Mode
Type of the option to
change
Tens position of the
option number
Units position of the
option number
New value
Indication 0 D 2 1 7 1
CAUTION
If your indoor units support both cooling and heating, the mixed operation (two or more indoor units operate in different
modes simultaneously) is not available when the indoor units are connected to the same outdoor unit. If you set an indoor
unit as the master indoor unit by using the remote control, the outdoor unit automatically operate in the current mode of the
master indoor unit.