Setting indoor unit addresses and installation option
48
English
Installation manual
Main Address
Press the 'OK' button to complete the setting.
New address
0 8
20 00 01
Target Address
RMC Address
Press the 'OK' button to complete the setting.
New address
0 8
20 00 01
Target Address
[Address > Main Address] [Address > RMC Address]
Address setting range : Main (0 ~ 4F) / RMC (0 ~ FE)
NOTE
• Press the button anytime during setup to exit without setting.
• Address will not be applied if you don’t press button.
• Setting the Main/RMC Address of an Indoor unit is available only with a Main wired remote control.
Setting an indoor unit installation option
1 If you want to use the various additional functions for your Wired Remote control, press the and buttons at the
same time for more than 3 seconds.
• The password entry screen appears.
2 Enter the password, “0202,” and then press the button.
• The settings screen for installation/service mode appears.
3 See the list of additional functions for the Wired Remote control on the next page, and then select the Installation Option 1
menu.
• Once you have entered the settings screen, the current setting appears.
• Refer to the chart for data setting.
• Using the / buttons, change the settings and press the button to move to the next setting.
• Press the button to save the new setting.
• Press the button to move to the Home screen.
NOTE
• While setting the data, you can press the button to move to the Home screen after checking the saving status at
a pop-up screen.