Setting indoor unit addresses and installation option
50
English
Installation manual
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2
RESERVED
External room temperature sensor
/Minimizing fan operation when the
thermostat is off
Central control
RESERVED
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1
Drain pump &
Emergency Stop
Hot Coil
Auxiliary heater
Controller variables for
the auxiliary heater
RESERVED
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2
External control
External control
output
RESERVED
Buzzer
Maximum filter
usage time
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3
Individual control of a
remote control
Heating setting
compensation
RESERVED
Away Set OFF Timer
RESERVED
NOTE
• Press
button anytime during setup to exit without setting.
• Option code will not be applied if you don’t press button.
• The setting Installation option code is available only with a Main wired remote control.
• Setting Installation option code is available when there is one-on-one connection between a wired remote control
and an indoor unit.