Installation manual
Installation options for the 02 series
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 Evaporator Drying
Use of external room
temperature sensor /
Minimizing fan operation
when thermostat is off
Use of central
control
FAN RPM
compensation
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 Use of drain pump Use of hot water heater
Settings for load operation
during heater control
Fan control during defrost
mode / heater control
during defrost mode
EEV Step when
heating stops
-
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 Use of external control
Setting the output
of external control /
External heater signal
/ Cooling operation
signal / Free Cooling
control signal
S-Plasma ion
Buzzer control /
whether to use
humidity sensor /
whether to use APP
UX DSP (Dual Set
Point) / whether to
use R-32 sensor
Hours of filter usage
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3
Individual control of a
remote controller
Heating setting
compensation /
Removing condensate
water in heating mode
Adjusted EEV step of
stopped unit during oil
return /defrost mode.
- -
Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to 2 (the drain pump is used with 3 minute delay).
If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).
If you set an option to a value that is out of range specified above, the option is automatically set to 0 by default.
The SEG5 option (Use of central control) is set to 1 (Use) by default. Therefore, you don’t need to set the SEG5 option additionally.
Note that even if the central control system is not connected, no errors occur. If you want a specific indoor unit not to be controlled
by the central control system, set the SEG option of that indoor unit to 0 (Disuse).
The external output of SEG15 is generated via MIM-B14 connection. (Refer to the manual of MIM-B14.)
If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1).
COM1
Outdoor
Communication
Wire Remote
Controller
AC
POWER
HOT
COIL
DC 12 V
COM2(+) L N(-)
The output of hot coil terminal is AC 220 V / 230 V
(The same as Indoor Unit’s input Power)