26
Field setting mode
English
Field Setting Mode
Field Setting Value (FSV) 20**
Code 20** : Water law design and external room thermostat Heating(2 WL’s for floor & FCU),
Cooling(2 WL’s for floor & FCU), WL & Thermostat types
࡙ The values in the following table are just examples for your understanding.
Main Menu
&
Code
Menu
Function
Sub
Code
MODEL CODE :
AE200(260)RNW***
MODEL CODE :
MIM-E03CN
Setting Standard Setting Standard
Item Step Unit Default Min. Max. Default Min. Max.
Water Law
Code 20**
Heating
Outdoor
Temperature for
Heating Water Law
Max (Point
1
)
1 ঐ 2011 -10 -20 5 -10 -20 5
Min (Point
2
)
1 ঐ 2012 15 10 20 15 10 20
Water out
Temperature for
WL1 Heating
(UFHs)
Max (Point
1
)
1 ঐ 2021 40 17 65 40 17 65
Min (Point
2
)
1 ঐ 2022 25 17 65 25 17 65
Water out
Temperature for
WL2 Heating
(FCUs)
Max (Point
1
)
1 ঐ 2031 50 17 65 50 17 65
Min (Point
2
)
1 ঐ 2032 35 17 65 35 17 65
Heating Water Law
Selection
WL Type - - 2041 1(WL1) 1 2 1 (WL1) 1 2
Cooling
Outdoor
Temperature for
Cooling Water Law
Max (Point
1
)
1 ঐ 2051 30 25 35 30 25 35
Min (Point
2
)
1 ঐ 2052 40 35 45 40 35 45
Water out
Temperature for
WL1 Cooling (UFHs)
Max (Point
1
)
1 ঐ 2061 25 5 25 25 5 25
Min (Point
2
)
1 ঐ 2062 ߢߩ 525 ߢߩ 525
Water out
Temperature for
WL2 Cooling
(FCUs)
Max (Point
1
)
1 ঐ 2071 ߢߩ 525 ߢߩ 525
Min (Point
2
)
1 ঐ 2072 5 5 25 5 5 25
Cooling Water Law
Selection
WL Type - - ߣߡߩߢ 1(WL1) 1 2 1(WL1) 1 2
External
Control
External Room
Thermister
#1 (UFHs) 1 - 2091 0(No) 0 4 0(No) 0 4
#2 (FCUs) 1 - 2092 0(No) 0 4 0(No) 0 4
Remote
Controller
Remote Controller Room Temp.
Control
1-20934 14 4 14