Field Setting Mode
Field Setting Value (FSV) 50**
Code 50** : User’s options for extra functions
The values in the following table are just examples for your understanding.
Main
Menu &
Code
Menu
Function
Sub
Code
MODEL CODE :
AE200 (260)RNW***
MODEL CODE :
MIM-E03CN
Setting Standard Setting Standard
Item Step Unit Default Min. Max. Default Min. Max.
Others
Code
50**
Outing Mode
Water Out
Temperature
for Cooling
1 ઑA 5011 25 5 25 25 5 25
Room Temperature for
Cooling
1 ઑA 5012 30 ߢߩ 30 30 ߢߩ 30
Water Out
Temperature
for Heating
1 ઑA 5013 15 15 55 15 15 55
Room Temperature for
Heating
1 ઑA 5014 16 16 30 16 16 30
Cooling WL1 Temp. 1 ઑA 5015 25 5 25 25 5 25
Cooling WL2 Temp. 1 ઑA 5016 25 5 25 25 5 25
Heating WL1 Temp. 1 ઑA 5017 15 15 55 15 15 55
Heating WL2 Temp. 1 ઑA ߦߡߢߩ 15 15 55 15 15 55
DHW tank Temp. 1 ઑA 5019 30 30 70 30 30 70
DHW Saving
DHW Saving Temp 1 ઑA 5021 5 0 40 5 0 40
DHW Saving Mode 1 - 5022 0 0 1 0 0 1
DHW Saving Thermo
on Temp.
1 ઑA 5023 25 0 40 25 0 40
Power Peak Control
Application - - 5041 0 (No) 0
1
(Yes)
0 (No) 0
1
(Yes)
Select forced off parts 1 - 5042 0 (All) 0 3 0 (All) 0 3
Using input voltage - - 5043 1 (High) 0 (Low) 1 1 (High)
0
(Low)
1
Frequency Ratio Control - - 5051 0 (No) 0
1
(Yes)
0 (No) 0
1
(Yes)