Field Setting Mode
Classification Function Detail
Code
(Main
+ sub
menu)
Basic Min. Max. Step Unit
DHW
Disinfection
Operation 3041 1 (Yes) 0 (No) 1 - -
Operation interval 3042 Fri (5)
Sun
(0)
AllDay (7) - day
Start time 3043 23 0 23 1 hour
Target temp. 3044 70 40 70 5 °C
Holding time 3045 10 5 60 5 min.
Max. operation time 3046 ߩ 1241hour
Solar heat panel / defrost
signal
Solar heat panel H/P
interlocking / defrost
signal
3061 0 0 3 - -
Heating Heating mode
Heating/hot water
priority
4011
0 (Hot
water)
0
1
(Heating)
--
Heating priority 4012 0 -15 20 1 °C
Heating Off 4013 35 14 35 1 °C
Others
Outing mode
Temperature of cooling
water oulet
5011 25 5 25 1 °C
Room Temperature of
cooling Mode
5012 30 ߢߩ 30 1 °C
Temperature of heating
leaving water
5013 15 15 50 1 °C
Indoor heating
temperature
5014 16 16 30 1 °C
Temperature of auto
heating WL1 water
5017 15 15 50 1 °C
Temperature of auto
heating WL2 water
ߦߡߢߩ 15 15 50 1 °C
Temperature of hot
water Tank
5019 30 30 75 1 °C
Economic DHW mode
Temperature of hot
water Tank
5021 5 0 40 1 °C
Smart grid (Power peak
control)
Operation 5041 0 (No) 0 1 (Yes) - -
Heat source for
operation limit
5042 0 (All) 0 2 1 -
Contact Logic 5043
1
(High)
0
(Low)
1--