37
Field Setting Mode
Field Setting Value (FSV) 40**
Code 40** : User’s options for heating devices including internal backup heater and external boiler
• The values in the following table are just examples for your understanding.
Main Code Menu
Function
Sub
Code
MODEL CODE : AE***DN*MPK /
AE***DN*SPG / MIM-E03FN
MODEL CODE : AE***DN*THP
Setting Standard Setting Standard
Item Step Unit Default Min. value Max. value Default Min. value Max. value
Heating
Code 40**
Heating
Heat
Pump
Heating / DHW priority - - 4011 0 (DHW) 0 1 (Heating) 0 (DHW) 0 1 (Heating)
Low Outdoor Temp. for
Heating Priority
1 4012 0 -15 20 0 -15 20
Heating Off Temp . 1 4013 35/45
(*2)
10 35/45
(*2)
35 10 35
Backup
Heater
On/Off - - 4021 0 (No) 0 1 0 (No) 0 1
BUH/BSH Priority 1 - 4022
2 (BSH)
(*3)
2
(*3)
2
(*3)
2 (BSH)
(*3)
0
(*3)
2
(*3)
0 (Both)
(*4)
0
(*4)
2
(*4)
0 (Both)
(*4)
0
(*4)
2
(*4)
Back-up Heater On/Off - - 4023 1 (Yes) 0 (No) 1 1 (Yes) 0 (No) 1
Threshold Temp. 1 4024 0 -25 35 0 -25 35
Defrost Backup Temp. 5 4025 15 10 55 15 10 55
External Heater - - 4026 0 0 1 N/A N/A N/A
Backup
Boiler
Back-up Boiler On/Off - - 4031 0 (No) 0 1 (Yes) 0 (No) 0 1 (Yes)
Boiler Priority - - 4032 0 (No) 0 1 (Yes) 0 (No) 0 1 (Yes)
Threshold Condition 1 4033 -15 -20 5 -15 -20 5
Mixing
valve
Application 1 - 4041
2 (Yes)
(*5)
0
(*5)
2
(*5)
2 (Yes)
(*5)
0
(*5)
2
(*5)
0 (No)
(*6)
0
(*6)
2
(*6)
0 (No)
(*6)
0
(*6)
2
(*6)
1 4042 10 5 15 10 5 15
1 4043 10 5 15 10 5 15
Control factor 1 - 4044 2 1 5 2 1 5
Control interval 1 min 4045 1 1 30 1 1 30
Running Time 1 (x10) sec 4046 12 6 24 12 6 24
Inverter
Pump
Application - - 4051 1 0 3 1 0 3
1 4052 5 2 8 5 2 8
Control factor 1 - 4053 2 1 3 2 1 3
PWM minimum output 1 -10% 4054 0 (25%) 0 (25%) 3 (55%) 0 (25%) 0 (25%) 3 (55%)
DB68-12922A-02_IB_24Y EHS AE7000D_EU_EN_.indd 37DB68-12922A-02_IB_24Y EHS AE7000D_EU_EN_.indd 37 2024-12-11 오전 10:04:422024-12-11 오전 10:04:42