Field Setting Mode
Air to Water Heat Pump: Only AE***DN**** / MIM-E03FN Model
CAUTION
Set the FSV value of the product other than the specified models by referring to the FSV label provided
with the manual of the product, and then attach it on the control box's cover. The FSV values in the table
are applied to the specified models.
NOTE
Be sure to reset the power when changing the FSV (#3041 to 3046) of disinfection operation and the
FSV (#5011 to 5019) of setting the Away mode.
Field Setting Value (FSV) 10**
Code 10** : Upper and lower temperature limits of each operation mode of AI Home
Heating (Water Out, Room), Cooling (Water Out, Room), DHW (Tank)
The values in the following table are just examples for your understanding.
Main Code Menu
Function
Sub
Code
Remark
F.S.
Value
MODEL CODE : AE***DN*MPK /
AE***DN*SPG / MIM-E03FN
MODEL CODE :
AE***DN*THP
Setting Standard Setting Standard
Item Step Unit Default
Min.
value
Max. value Default
Min.
value
Max.
value
Wired
Controller
Code 10**
Cooling
Water Out
Temperature for
Cooling
Max 1  1011 25 18 25 25 18 25
Min 1  1012 16 5 18 16 5 18
Room Temperature
for Cooling
Max 1  1021 30 28 30 30 28 30
Min 1  1022 18 18 28 18 18 28
Heating
Water Out
Temperature for
Heating
Max 1  1031 65/70/75
(*1)
37 65/70/75
(*1)
55 37 55
Min 1  1032 25 15 37 25 15 37
Room Temperature
for Heating
Max 1  1041 30 18 30 30 18 30
Min 1  1042 16 16 18 16 16 18
DHW
DHW tank
Temperature
Max 1  1051 55/63/70
(*1)
50 70 50 50 70
Min 1  1052 40 30 40 40 30 40
Hysteresis for
Thermo ON
Water Out Hysteresis
for Heat
0.5  1061 0 0 7 0 0 7
Water Out Hysteresis
for Cool
0.5  1062 1 1 7 1 1 7
Room Hysteresis for Heat 0.5  1063 0 0 7 0 0 7
Room Hysteresis for Cool 0.5  1064 1 1 7 1 1 7
NOTE
The FSV #3011 in the AI Home should be set to 1 or 2 to use the DHW mode.
(*1)
The value is determined according to the type of outdoor unit.
Field setting mode