2nd Edition of TEMP2000_Series IM : July. 16. 2010 Page 59 / 87
Description on HIGH, LOW Deviation Operation
HIGH Deviation Operation
When Middle SP < Process Value(PV) High Limit SP
Process Value (PV) ≥ Setting Point (SP) + HIGH Deviation : Operation becomes ‘ON’.
Process Value (PV) < Setting Point (SP) + HIGH Deviation : Operation becomes ‘OFF.
LOW Deviation Operation
When Low Limit SP Process Value (PV) < Middle SP
Process Value (PV) ≥ Setting Point (SP) – LOW Deviation : Operation becomes ‘ON’.
Process Value (PV) < Setting Point (SP) – LOW Deviation : Operation becomes ‘OFF.
Refer to [8.2 ON/OFF Signal Operation]