CWFL-6000 Series
External input standby
activation delay
Conductivity alarm activation
setting
With conductivity ON /
Without conductivity
OFF
Ultra-high conductivity alarm
setting value
Relay NO/NC setting under
lower limit of conductivity
NO-normally opened
NC-normally closed
Relay output setting under
lower limit of conductivity
Ultra-low conductivity alarm
setting value
Self-starting after being
electrified
Key lock of Chiller On/Off
NOTE:
(1) In parameter setting status, the system runs under original parameters;
(2) Under Constant Temperature control mode (“ F4” and “F8” set at 0), water
temperature is controlled by “F1” and “F5”;
(3) Under Intelligent Control mode (“ F4” and “F8” set at 1), water temperature
is self-adjusting according to ambient temperature. The temperature
difference is controlled by “F2” and “F6”.
(4) The low temp section and high temp section of the chiller can be set
different control modes.
3. Failure warning processing mode
When alarm occurs, the failure alarm code will be displayed on the upper right
corner of the LCD screen. In alarming state, the alarm sound could be
suspended by pressing any button, but the alarm display remains until the
alarm condition is eliminated.
4. Failure code table
Communication
failure alarm
E00 shown with
alarm sound
Automatic clearing
after mainboard
and operation panel
are connected well
Low temp. system
flow alarm
E01 shown with
alarm sound
The compressor, condenser fans
and heater of the high/low
temp. system shut down