S&C Instruction Sheet 681-530 37
If the coordination settings selections are invalid, or contradictory, an error message
explaining the problem will appear, and any cell with an invalid value will be highlighted
in yellow after clicking on the Save button. Please note that selections will not be saved
until the error is fixed. See Figure 34.
Figure 34. A Time Overcurrent Phase Protection Error message.
STEP 4. When programming the overcurrent control is completed, make sure to replace
the data-port cover and ensure it is secure. S&C recommends re-checking the
control settings on the Status screen before leaving the overcurrent control.
NOTICE
Make sure the data-port cover is secure after programming the control. Failure to
secure the data-port cap may result in damage to the data port. A control with a
damaged data port cannot be accessed via personal computer.
Programming the Overcurrent Protection Settings