44 S&C Instruction Sheet 681-530
If a factory-default reset is initiated, the overcurrent control is provided with the factory-
default protective settings shown in Table 4 for both Interrupter 1 and Interrupter 2:
Table 4. Factory Default Protective Settings
Phase A Phase B Phase C Ground
Negative
Sequence
Sensitive
Earth Fault
Time Overcurrent Phase Protection Element
Protection Element ENABLED ENABLED ENABLED DISABLED DISABLED DISABLED
Curve Family Vista Speed Vista Speed Vista Speed Vista Coord. Vista Coord. Vista Coord.
Inverse Segment E E E Tap Tap Tap
Ampere Rating 200E 200E 200E 400 400 400
Minimum-Trip
Current, A
483 483 483 400 400 400
Time Multiplier 1.00 1.00 1.00 1.00 1.00 1.00
Time Adder, s N/A N/A N/A N/A N/A N/A
Low-Current Cutoff
Low-Current Cutoff DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED
Low-Current Cutoff, A 1.00 1.00 1.00 1.00 1.00 1.00
Definite Time Phase Protection Element #1
Protection Element DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED
Definite-Time
Current, A
1.00 1.00 1.00 1.00 1.00 1.00
Definite-Time Time, s 0.000 0.000 0.000 0.000 0.000 0.000
Definite Time Phase Protection Element #2
Protection Element DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED
Definite-Time
Current, A
1.00 1.00 1.00 1.00 1.00 1.00
Definite-Time Time, s 0.000 0.000 0.000 0.000 0.000 0.000
Reset Time Parameters
Reset Type Timed Timed Timed Timed Timed Timed
Reset Time, s 0.000 0.000 0.000 0.000 0.000 0.000
NOTICE
S&C Electric Company programs the Global Settings (Nominal Frequency,
Continuous Current, Interrupting Rating, and Trip Mode) at the factory to match
the configuration of the Vista switchgear. The Factory Default Reset setting
will restore the settings back to the overcurrent control pre-programmed state.
You MUST reprogram the Global Settings for the overcurrent control after
performing a factory reset to match the configuration of the Vista switchgear
that the overcurrent control is monitoring and controlling. Improper operation
of the control and/or switchgear may result if global settings do not match the
Vista Switchgear model. See “Programming the Control Settings” on page 28 for
instructions on how to reprogram the Global Settings.
The Factory Default Reset setting, which is available under the Control Settings tab,
will restore the control to its pre-programmed state. When a Factory Default Reset
command is initiated, the following settings will be restored:
Global Settings:
Continuous Current: 600 A
Fault Interrupting Rating: 12.5 kA
Trip Mode: Single-phase trip/single-phase lockout
All protective settings under the Interrupter 1 and Interrupter 2 menus (These will be
restored to the “Factory Default Protective Settings.” See Figure 4.
Both the admin and user passwords will be reset to the factory-default values.
Factory Default
Protective Settings
Factory Default Reset
Factory Defaults and Factory Default Reset