S&C Instruction Sheet 681-530 25
Understanding the Status Display
The Status screen and menus provide a summary of the status of the overcurrent control,
measurement of the load current of the associated fault interrupters, and the control
settings. It also provides a summary of the login status, the overcurrent control serial
number and MAC address, and the rmware installed on the control. This page can be
viewed from admin and user logins and when using the View button.
The overcurrent control has a physical LED status display located on the outside of
the electronics module that is visible when the overcurrent control is removed from its
enclosure. An on-screen replica of this status display can be viewed when a computer is
connected to the control. See Figure 23. See Table 2 for the LED key.
Figure 23. The Status screen.
Table 2. Status Display LED Key
LED Key Description
Orange Trip operation recorded
Red Element initiated trip
Green
Flashing: Control OK
Solid: Control Error
White All prior trip operations cleared