S&C Instruction Sheet 681-530 39
Overcurrent Protection Setting Denitions
The Definite Time Phase Protection #1 element must be enabled for the Defi-
nite Time Phase Protection #2 element to be enabled. When programming both the
Definite Time #1 element and the Definite Time #2 element, the Definite Time #2
element must be set at a higher current and a faster speed than the Definite Time #1
element or an error will occur. The Definite Time #1 and #2 elements also must be
greater than the Low-Current Cutoff setting and the minimum trip current. The time
must be faster than the time-overcurrent protection curve.
Denite-Time Current, A – This is the current at which the Denite Time Current
element picks up.
Denite-Time Time, s – This is the time delay after the Denite-Time Current value
is exceeded at which the Denite Time element initiates a trip.
Reset Time Parameters (Time Overcurrent Phase Protection)
Reset Type – The Reset parameter is a denite time reset method and the Type eld is
always set to Timed mode.
Reset Time, s – Enter the time delay for the denite time reset, if desired. Accumulated
value will reset to zero after Reset Time setting has elapsed.
(Ground Protection) Protection Element – Select to enable or disable protection
settings for the selected way. The Ground Protection element trips the fault interrupter
when the computed residual of the three-phase current exceeds the minimum trip current
for the time value set by the Inverse Curve or Denite Time settings.
Curve Family – Select the TCC Curve Family: IEC, IEEE, or Vista Coordination curve.
For more details on the curve families, see the “Overcurrent Control Settings” section
on page 56 for the curve families available. The TCC curves available can also be found
in S&C Information Bulletin 680-211, “Time-Current Characteristic Curves.”
Inverse Segment – Select the desired segment from the drop-down list of curves.
Ampere Rating – Select the ampere rating from the drop down menu for Vista
Coordination TCCs. The IEEE and IEC curves do not use the Ampere Rating eld.
Minimum-Trip Current, A – This is the current at which the inverse curve begins timing.
When using Vista coordination curves, the minimum-trip current is set automatically
according to the ampere rating selected. For IEEE and IEC curves, enter the Minimum
Trip Current value in increments of 1 ampere. The value should always be equal to or
lower than the low-current cutoff.
Time Multiplier – This is the time multiplier for the inverse curve. The time multiplier
is only used with IEEE and IEC curves.
Time Adder, s – This is the time adder for the inverse curve. The time adder is only used
with IEEE and IEC curves.
Ground Protection