Installation and User Instructions
Aquaheat Unvented Water Heaters
Models: AH7/2.2, AH10/2.2, AH15/2.2
Please read and understand these instructions before starting work.
Please leave this leaet with the user following installation
PACK CONTENTS
Heater, Pressure relief valve, Fixing screws and plugs,
Installation and User Instructions.
WARNING
This water heater must only be installed by qualied persons.
36005791 Issue 3.
Question and Answer IconNeed help?

Do you have a question about the Santon AH7/2.2 and is the answer not in the manual?

Summary

Technical Specification

Important Installation Points

Pressure Relief Valve Requirement

Mandates fitting a Pressure (Expansion) Relief Valve for installation and guarantee.

Cold Water Expansion Conditions

Details conditions for cold water expansion within the supply system.

Expansion Vessel for Non-Compliant Conditions

Specifies using an Expansion Vessel when 1.2 conditions cannot be met.

Pressure Reducing Valve for High Static Pressure

Requires a Pressure Reducing Valve if static supply pressure exceeds 4.1 bar.

Temperature;Pressure Relief Valve Option

Describes the option to fit a Temperature/Pressure Relief Valve on site.

General Installation Requirements

Unit Mounting and Placement

Details vertical wall mounting, floor mounting, and space for connections.

Wall Support and Services Check

Emphasizes verifying wall capacity and checking for hidden services.

Pipework and Connections

Describes pipe labeling, material, size, and compression fittings.

Installation Warnings

Advises against solder joints and plumbers paste to prevent damage.

Electrical Installation Requirements

Electrical Supply and Cable

Specifies the cable type, fused supply, and double pole isolating switch.

Wire Colour Coding

Lists the colour codes for Earth, Live, and Neutral wires.

Discharge Pipe Requirements

Discharge Pipe Connection and Flow

Connect discharge outlet to pipe, ensure continuous fall and no obstructions.

Pipe Sizing and Material

Specifies minimum pipe sizes (15mm, 22mm) and material for 100°C water/steam.

Safe Discharge Point

Final discharge point must be safe and visible.

Commissioning

Pre-Power Checks and Filling

Fill unit with water, check leaks before switching on electricity.

Purging and Leak Check

Open hot tap to purge air and flush pipework, then check for leaks.

Safety Valve Operation Test

Manually test Pressure/Temperature Relief Valves to ensure water flows freely.

Power On and Temperature Setting

Switch on power, observe indicator light, adjust thermostat for desired temperature.

Terminal Cover Removal and Fitting

Terminal Cover Removal

Instructions for removing the terminal cover using a screwdriver.

Terminal Cover Fitting

Guidelines for refitting the terminal cover securely.

Maintenance - Descaling

Preparation for Descaling

Switch off supplies, relieve pressure, disconnect plumbing and remove unit.

Element Plate Removal and Cleaning

Remove terminal cover, disconnect wiring, remove element plate, clean scale.

Re-assembly and Re-commissioning

Refit element plate with new gasket, rewire, and recommission unit.

Maintenance - Safety Valves

Regular Safety Valve Checks

Manually operate safety valves to ensure water flows freely and they reseat correctly.

Maintenance - Expansion Vessel Precharge Pressure

Checking and Recharging Expansion Vessel

Check pre-charge pressure (4.1 bar), recharge if low using a tyre pump.

Spare Parts

Fault Finding

Water Not Heating Faults

Troubleshoot electrical supply, thermal cut-out, or thermostat issues.

Discharge from Relief Valves

Address issues like excessive pressure, expansion, or valve faults.

No Water Flow Faults

Check inlet valve fitting, mains supply, or blockages.

Milky Water Fault

Identify milky water as oxygenated water that will clear.

Accessories

User Instructions

Temperature Setting and Freezing Prevention

Set thermostat (6-66°C); keep powered on and set low in winter to prevent freezing.

Indicator Light Function

The indicator light shows when the unit is actively heating.

Periodic Maintenance

Ensure optimal performance through periodic maintenance as per instructions.

Important Safety Notes for Users

Do not block safety valves; switch off power immediately if water discharges.

Guarantee

Environmental Information

Summary

Technical Specification

Important Installation Points

Pressure Relief Valve Requirement

Mandates fitting a Pressure (Expansion) Relief Valve for installation and guarantee.

Cold Water Expansion Conditions

Details conditions for cold water expansion within the supply system.

Expansion Vessel for Non-Compliant Conditions

Specifies using an Expansion Vessel when 1.2 conditions cannot be met.

Pressure Reducing Valve for High Static Pressure

Requires a Pressure Reducing Valve if static supply pressure exceeds 4.1 bar.

Temperature;Pressure Relief Valve Option

Describes the option to fit a Temperature/Pressure Relief Valve on site.

General Installation Requirements

Unit Mounting and Placement

Details vertical wall mounting, floor mounting, and space for connections.

Wall Support and Services Check

Emphasizes verifying wall capacity and checking for hidden services.

Pipework and Connections

Describes pipe labeling, material, size, and compression fittings.

Installation Warnings

Advises against solder joints and plumbers paste to prevent damage.

Electrical Installation Requirements

Electrical Supply and Cable

Specifies the cable type, fused supply, and double pole isolating switch.

Wire Colour Coding

Lists the colour codes for Earth, Live, and Neutral wires.

Discharge Pipe Requirements

Discharge Pipe Connection and Flow

Connect discharge outlet to pipe, ensure continuous fall and no obstructions.

Pipe Sizing and Material

Specifies minimum pipe sizes (15mm, 22mm) and material for 100°C water/steam.

Safe Discharge Point

Final discharge point must be safe and visible.

Commissioning

Pre-Power Checks and Filling

Fill unit with water, check leaks before switching on electricity.

Purging and Leak Check

Open hot tap to purge air and flush pipework, then check for leaks.

Safety Valve Operation Test

Manually test Pressure/Temperature Relief Valves to ensure water flows freely.

Power On and Temperature Setting

Switch on power, observe indicator light, adjust thermostat for desired temperature.

Terminal Cover Removal and Fitting

Terminal Cover Removal

Instructions for removing the terminal cover using a screwdriver.

Terminal Cover Fitting

Guidelines for refitting the terminal cover securely.

Maintenance - Descaling

Preparation for Descaling

Switch off supplies, relieve pressure, disconnect plumbing and remove unit.

Element Plate Removal and Cleaning

Remove terminal cover, disconnect wiring, remove element plate, clean scale.

Re-assembly and Re-commissioning

Refit element plate with new gasket, rewire, and recommission unit.

Maintenance - Safety Valves

Regular Safety Valve Checks

Manually operate safety valves to ensure water flows freely and they reseat correctly.

Maintenance - Expansion Vessel Precharge Pressure

Checking and Recharging Expansion Vessel

Check pre-charge pressure (4.1 bar), recharge if low using a tyre pump.

Spare Parts

Fault Finding

Water Not Heating Faults

Troubleshoot electrical supply, thermal cut-out, or thermostat issues.

Discharge from Relief Valves

Address issues like excessive pressure, expansion, or valve faults.

No Water Flow Faults

Check inlet valve fitting, mains supply, or blockages.

Milky Water Fault

Identify milky water as oxygenated water that will clear.

Accessories

User Instructions

Temperature Setting and Freezing Prevention

Set thermostat (6-66°C); keep powered on and set low in winter to prevent freezing.

Indicator Light Function

The indicator light shows when the unit is actively heating.

Periodic Maintenance

Ensure optimal performance through periodic maintenance as per instructions.

Important Safety Notes for Users

Do not block safety valves; switch off power immediately if water discharges.

Guarantee

Environmental Information