6-8
6
List of Item Codes (Some item codes cannot be set due to the type of models.)
Parameter
Item code
01 Control system schedule
02 Control system schedule
03 Control system schedule
04 Snowfall sensor operation
0 = No sensor, control performed
1 = No sensor, control not performed
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
Do not set
22 = 22 o'clock (at shipment)
00 = 00 minute (at shipment)
0 = 50dB(A) mode , 1 = 45dB(A) mode
Do not set
Do not set
Do not set
Do not set
2 = Sensor present, control performed
3 = Sensor present, control not performed
05 Control system schedule
Do not set
06 Control system schedule
Do not set
07 Ignore capacity
0 = Disabled 1 = Ignores capacity ratio
08 Control system schedule
09 Control system schedule
0A Control system schedule
0b Control system schedule
0C Forced operation of
0 = Disabled
indoor unit drain pump
1 = During cooling only, 2 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
2 = During cooling only, 4 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
3 = At all times, 4 hours stopped + 20 minutes operating
4 = At all times, 2 hours stopped + 20 minutes operating
0d Control system schedule Do not set
1 = Cooling only0 = Heat pump
1 = Available0 = Non
Cooling only0E
0F Control system schedule
10 Control system schedule
11 Multi-floor installation
12 Control system schedule
13 Control system schedule
20 Cool OL control
21 Silent mode
70% ~ 100% (40% ~ 160% setting capable)Demand 150
70% ~ 100% (40% ~ 160% setting capable)Demand 251
52 Current control level 70% ~ 100% , -1 (No control) (40% ~ 160% setting capable)
57
58
59
5A
5B
* Figures in parentheses indicate the data at the time of shipment from the factory.
Silent mode starting time (hour)
Silent mode starting time (minute)
08 = 8 o'clock (at shipment)Silent mode finishing time (hour)
00 = 00 minute (at shipment)Silent mode finishing time (minute)
0 = Normal (at shipment) 1 = Auto silent 2 = Capacity prioritySilent mode
SM830161Book.indb8SM830161Book.indb8 2008/05/279:33:202008/05/279:33:20