1-52
1
1-2. Major Component Specifi cations
(A) Indoor Units
4-Way Air Discharge Semi-Concealed Type SPW-XDR484GH56 (A/B), X485H
MODEL No.
SPW-XDR484GH56 (A/B), X485H
Source
220 - 230 - 240V, single-phase, 50/60Hz
Controller P.C.B. Ass'y
CR-SXRP56B-B (Microprocessor)
Fan (Number...diameter, depth)
Turbo (1...ø460, 200)
Fan motor
Model...Nominal output W DK8-93C280H...90W
Source 280/340V (DC), 3-phase
No. of pole...rpm (230V, High) rpm 8P...620
Coil resistance
(Ambient temperature 20°C)
Ω
RED–WHT : 43.0
WHT–BLK : 43.0
BLK–RED : 43.0
Run capacitor VAC, µF –
Safety device
overcurrent, rotating signal detection, fuse
Electronic expansion valve
Coil –
Coil resistance (at 20°C)
Ω
–
Valve body –
Heat Exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 2...1.25
Face area m
2
0.584
Panel
Indoor unit
Model No. PNR-XD484GHAB (optional)
Dew proof heater –
Auto louver motor MP24GA
Coil resistance (at 20°C)
Ω
380 ± 7% / phase
Drain Pump
ADP-1414
Rated VAC, W AC230V, 50Hz, 12W
Total head & capacity 500mm, 400cc/min