1-53
1
1-2. Major Component Specifi cations
(A) Indoor Units
4-Way Air Discharge Semi-Concealed Type SPW-XM185H
MODEL No.
SPW-XM185H
Source
220 - 230 - 240V, single-phase, 50/60Hz
Controller P.C.B. Ass'y
CR-XM075XH (Microprocessor), POW-XM075XH
Fan (Number...diameter, depth)
Turbo (1...ø322, L147)
Fan motor
Model...Nominal output W SIC-72FV-D866-1...66W
Source 280/340V (DC), 3-phase
No. of pole...rpm (230V, High) rpm 8P...750
Coil resistance
(Ambient temperature 20°C)
Ω
–
Run capacitor VAC, µF –
Safety device
overcurrent, rotating signal detection, fuse
Electronic expansion valve
Coil –
Coil resistance (at 20°C)
Ω
–
Valve body –
Heat Exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 2...1.4
Face area m
2
0.27
Panel
Indoor unit
Model No. PNR-XM185 (optional)
Dew proof heater –
Auto louver motor MP24ZN-12V
Coil resistance (at 20°C)
Ω
380 ± 7% / phase
Drain Pump
PLD-12230ST-2
Rated VAC, W AC230V, 50Hz, 12W
Total head & capacity 850mm, 400cc/min
SM830161Book.indb53SM830161Book.indb53 2008/05/1920:33:122008/05/1920:33:12