1-74
1
1-3. Other Component Specifi cations
Concealed-Duct Type SPW-US185H
MODEL No.
Indoor Unit SPW-US185H
Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance
Thermal cut off temperature °C
Thermistor (Coil sensor): TH
PB2M-41E-SI5-1 E1,E2
Resistance
k
–10°C: 23.7±5% 20°C: 6.5±5%
–5°C: 18.8±5% 30°C: 4.4±5%
0°C: 15.0±5% 40°C: 3.1±5%
5°C: 12.1±5% 45°C: 2.6±5%
10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
KTEC-35-S6
Resistance
k
0°C: 16.5±5% 40°C: 2.7±5%
5°C: 12.8±5% 45°C: 2.2±5%
10°C: 10.0±5% 50°C: 1.8±5%
20°C: 6.3±5% 55°C: 1.5±5%
30°C: 4.0±5%
Electronic expansion valve
Valve body
Coil
Drain pump
PLD-12230ST-2
Rated
AC 230V, 12W
Float switch
FS-0218-102
Rated (Contact rated)
Contact open at float rising
SM830161Book.indb74SM830161Book.indb74 2008/05/1920:33:192008/05/1920:33:19