CONTROL MODULES
(
Cont.
)
Integral Action Method
This settin
g
determines the method of control b
y
the IAC.
Mode A or B A
Mode "A" controls such that the IAC takes into account the deadzone
and uses the end of the appropriate sta
g
e deadzone as the set value
point.
Mode "B" controls usin
g
the actual set value.
Integral Action Dumping
The IAC allows the use of inte
g
ral action in two different modes.
On or Off Off
If the parameter is set to Off then the IAC holds the current control
level when it enters its deadzone. This is done to avoid the IAC
droppin
g
strai
g
ht back out of the deadzone a
g
ain. Therefore, if the
IAC enters its deadzone with Sta
g
e 1 in operation, the IAC will hold the
Sta
g
e 1 at its current position rather than force the sta
g
e to a zero
position. If the controller exits the deadzone back to Sta
g
e 1, the
control action will resume at the previous point. If the controller exits
the deadzone in Sta
g
e 2, then Sta
g
e 1 and its inte
g
ral time would be
forced to zero before Sta
g
e 2 was allowed to run.
The opposite would be true if the controller went into deadzone with
Sta
g
e 2 operatin
g
.
If the parameter is set to On then the IAC zeros the operational sta
g
e
as the controller enters the deadzone. In some s
y
stems this ma
y
cause huntin
g
.
Boost Stage
This parameter selects which sta
g
e is boosted when the controller is in
a boost condition.
1 or 2 1
Boost in Occupied Period 1
This parameter selects whether the controller sta
g
e should be boosted
to 100% when it enters the first occupied period of each da
y
. The
boost will be held until the set value is reached if Inte
g
ral Action
Dumpin
g
is OFF. Controls to deadzone if Inte
g
ral Action dumpin
g
is
ON.
Yes or No No
Boost in Occupied Period 2
As for Boost is Occupied Period 1 but for the second occupied period
of each da
y
.
Yes or No No
Boost
(
review onl
y)
This parameter shows the influence boost is havin
g
on the currentl
y
active sta
g
e. As boost overrides the sta
g
e full
y
on.
On or Off
OPTIMISER MODULE
x 2
The optimiser module is self learnin
g
with optimum on and off,
selectable linear or BRESTART
(
lo
g
arithmic
)
optimisation and
histo
g
ram displa
y
. The optimiser can also be selected for heatin
g
or
coolin
g
plant operation.
The module has its own time schedule to set the occupanc
y
times.
Inputs to the module include space sensor, outside sensor
(
s
)
and
remote settin
g
. The module outputs are boost on and plant on which
would be connected to the controllers boost and occupied override
inputs respectivel
y
.
Main Sensor
(
review onl
y)
Displa
y
s the actual space sensor value.
–10,000 to 10,000
Actual Setpoint
(
review onl
y)
This displa
y
s the actual setpoint used b
y
the optimiser.
–10,000 to 10,000
Integral Action Dumping On
The optimiser set point must be e
q
ual to the controller set value minus
the appropriate deadzone.
Integral Action Dumping Off
The optimiser set point must e
q
ual the controller set value.
NOTE:-
If the remote set point input is used then it will set this value
and it will override the "Occupanc
y
Set point".
Remote Setpoint
(
review onl
y)
This is the actual value on the setpoint input of the optimiser module
and is usuall
y
set from an RPW.
–10,000 to 10,000
Optimum On Influence
(
review onl
y
, optional
)
This parameter displa
y
s the actual amount of time to be added to the
calculated boost time. This value is usuall
y
used to suppl
y
the
optimiser with an outside influence to take account of low
(
usuall
y
below 10
°
C
)
outside temperatures. This value is supplied to the
optimiser throu
g
h the influence analo
g
ue input. If this is an outside
influence it is derived from a look-up table module that is fed b
y
an
outside temperature sensor. This value is subtracted from the
optimum ON time.
–10,000 to 10,000
mins
Optimum Off Influence
(
review onl
y
, optional
)
As for Optimum On influence but the value is subtracted from the
calculated optimum off time.
–10,000 to 10,000
mins
MODULES AND FUNCTIONS
Bubbleland
Symbol Module Range Default
DS 2.951A 8 - 24 05/98