CONTROL MODULES
Cont.
Early Optimum Off
review onl
‘- - -’ is normall
displa
ed unless the optimiser is in an optimum off
period and the space temperature falls below the optimum off set point.
At this point the parameter displa
s the number of minutes left until the
end of occupanc
time. This same value is also output from the
module as an analo
ue si
nal.
0 to 10,000 mins - - -
Optimiser Running?
review onl
This allows
ou to see whether the optimiser has been disabled b
the
time lost input of the optimiser module.
Yes or No –
Learning is
review onl
This allows
ou to see whether the self learnin
has been disabled b
the optimiser module di
ital input or from the "Enable Learnin
"
parameter.
On or Off –
Schedule Mode
review onl
This code displa
s the section of the operatin
schedule the optimiser
is currentl
in.
Mornin
= before occupanc
.
Da
= durin
occupanc
.
Ni
ht = after occupanc
Mornin
, Da
,
Ni
ht
–
Optimiser Status
review onl
Displa
s the current status of the optimiser.
Waitin
= the optimiser is waitin
to start a boost or run down period.
Boostin
= boost is in pro
ress.
Terminate = function
i.e. boost, run down etc.
has been stopped.
Run down = run down is in pro
ress.
Waitin
,Terminate,
Boostin
, Run Down
–
Optimiser Time
review onl
This displa
s the current time as seen b
the optimiser.
0000 to 2359 –
Next Change Due
review onl
This displa
s the calculated time for the next chan
e of output for the
optimiser module.
If no calculation has been made because, for instance, the next da
is
off then ‘4800 waitin
’ is displa
ed.
0000 to 2359 and
Monda
to Sunda
–
Schedule
Displa
ed in a tabular format with one ON/OFF per da
s and a 7 da
week. The ON and OFF times must be set in 24 hour format i.e. 3:00
AM is set as 0300. If the time schedule is to be OFF for the da
then
the ON and OFF times should be set to 0000
Saturda
and Sunda
default to OFF
.
0000 to 2359 Monda
to
Frida
0800,1700
Saturda
to
Sunda
0000, 0000
Clear Histogram
This is used to clear the histo
ram data if re
uired.
Yes or No No
Occupancy Setpoint
This is the setpoint to be used b
the optimiser.
–10,000 to 10,000 19
NOTE:-
If the remote setpoint input is used then that will override the
Occupanc
Setpoint.
Optimiser Direction
This sets the optimiser to operate a heatin
or coolin
plant.
Heatin
or Coolin
Heatin
Optimiser Algorithm
This selects the t
pe of pre-heat used b
the optimiser. Lo
arithmic
pre-heat is based on the BRE recommended BRESTART curve and
linear is the standard Satchwell t
pe.
Linear or
Lo
arithmic
Linear
Design Pre-Heat
This parameter allows the desi
n pre-heat to be set in minutes per
input unit.
0 to 10,000
Mins/unit
20 Mins/unit
Advanced Pre-Heat
This parameter allows the advanced pre-heat to be set in minutes per
input unit.
This value is used in place of DPH if the preceedin
da
s
were off.
0 to 10,000
Mins/unit
25 Mins/unit
Enable Learning
This parameter is used to turn self learnin
on or off.
Yes or No Yes
Learning Ratio
This parameter sets the percenta
e self learnin
ratio.
0 to 100% 10%
Enable Optimum Off
This parameter is used to turn on and off the optimum off function.
Yes or No Yes
Design Optimum Off Time
This parameter allows the run down time to be set in minutes per input
unit.
0 to 10,000
Mins/unit
30 Mins/unit
Optimum Off Setpoint
This sets the minimum inside temperature at the end of the occupanc
period.
–10,000 to 10,000 19
ENTHALPY COMPARATOR MODULE
x 1
The Enthalp
Comparator module consists of two pairs of temperature
and humidit
inputs. The Enthalp
is calculated from each pair of
temperature/humidit
inputs. The output is on if the top pair of inputs
have a
reater enthalp
total heat content
than the bottom pair.
T
picall
this module is used to compare the enthalp
of the
recirculated air and fresh air and to override the controller to minimum
or maximum fresh air dependin
on application.
MODULES AND FUNCTIONS
Bubbleland
Symbol Module Range Default