48 Programming SATEL
5. F
IRE
(
FROM KEYPAD
) – signals the fire alarms triggered from keypad.
6. P
ANIC
(
FROM KEYPAD
) – signals the loud panic alarms triggered from keypad.
7. M
EDICAL ALARM
(
FROM KEYPAD
) – signals the medical assistance call alarm triggered from
keypad.
8. T
AMPER ALARM
– signals the tamper alarms.
9. DAY
ALARM
– signals the following:
alarms from 13. PANIC-
SILENT
type zones,
medical alarms from the 14. M
EDICAL
-
B
UTTON
and 15. P
ERSONAL EMERGENCY
type
zones,
alarms from 7. D
AY
/N
IGHT
type zones, if the partition to which the zone belongs is
disarmed,
alarms from 8. E
XTERIOR
type zones, if the armed mode which assumes that the user
will stay inside the protected facility is enabled in the partition (see: U
SER MANUAL
),
alarms from 4. P
ERIMETER
type zones, if the S
IGNALING DELAY
has been programmed for
them,
alarm from 5. I
NSTANT
and 6. E
XIT
type zones, if the B
ELL DELAY
option has been
enabled and the S
IGNALING DELAY
has been programmed for them,
alarms from zones, for which the R
EPORTING DELAY
option has been enabled, provided
they were violated during the E
NTRY DELAY
countdown,
unverified alarms, if the A
UDIBLE ALARM AFTER VERIFICATION
option is enabled for the
partition,
the first violation of the 8.
E
XTERIOR
type zones when they are armed, provided the
S
URVEILLANCE TIME
has been programmed for the zone,
violation of the counting zones (16-31 type zones) when armed.
10. DURESS
ALARM
– action carried out under duress – signals that a DURESS type code
(or prefix) has been used in the system.
11. C
HIME
– signals violation of the zones when they are disarmed.
12. S
ILENT ALARM
– activates in the same situations as the 9. DAY
A
LARM
output. Additionally,
it can signal silent panic alarms.
13. T
ECHNICAL ALARM
– signals alarms from zone types 40-56.
14. Z
ONE VIOLATION
– indicates the violations of zones.
15. V
IDEO ON DISARMED
– controlled by zones with the V
IDEO ON DISARMED
option enabled.
16. V
IDEO ON ARMED
– controlled by zones with the V
IDEO ON ARMED
option enabled.
17. READY
STATUS
– indicates whether the system is ready for arming, i.e. whether there are
no violated zones (active when there is no violation).
18. BYPASS
STATUS
– indicates the bypassing of zones.
19. E
XIT DELAY STATUS
– indicates the E
XIT DELAY
countdown.
20. E
NTRY DELAY STATUS
– indicates the E
NTRY DELAY
countdown.
21. A
RMED STATUS
– indicates the armed status of partitions.
22. F
ULL ARMED STATUS
– active if all selected partitions are armed.
23. A
RM
/D
ISARM BEEP
– signals:
starting the arming procedure (arming, if the exit delay has not been programmed) –
1 pulse;
disarming – 2 pulses;
clearing alarm – 4 pulses;
denial of arming or arming procedure failure – 7 pulses.