EasyManua.ls Logo

Satel Integra Plus Series - Telephone numbers; Starting the voice messaging

Satel Integra Plus Series
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SATEL INTEGRA Plus 75
program the codes for events which are to be reported.
5. Define the parameters of test transmissions.
10. Messaging
The control panel can inform you about the system events by means of:
voice messages (the INT-VG module or another voice synthesizer must be connected);
PAGER type text messages defined by the installer (the SATEL GSM modules enable the
PAGER messages to be converted into SMS);
SMS messages with the content consistent with event description in the event log (the
SATEL GSM module must be connected to the control panel).
The messaging by means of the voice messages and PAGER text messages can be
effected using the telephone line or GSM module. The SMS messaging can only be
effected using the GSM module (the RS-232 ports of control panel and module must
be connected):
GSM LT-1 with firmware 1.14;
GSM LT-2 with firmware 2.14;
GSM-4 with firmware 4.14;
GSM-5.
Messaging is performed independently from reporting but reporting has the priority. If in the
course of messaging some events occur which must be reported to the monitoring station by
the control panel, the messaging will be interrupted. The control panel will resume the
messaging function after the event codes are reported to the monitoring station.
You can program the messaging:
using the keypad, in the service mode, by means of the functions available in the
submenu;
– V
OICE MESSAGING
(voice messaging and messaging by means of the installer defined
text messages);
– SMS
MESSAGING
(messaging by means of SMS messages with content consistent with
event description in the event log).
using the D
LOAD
X program, in the "Messaging" window.
For the messaging function to work properly, some system options may have to be enabled.
10.1 Voice / PAGER messaging parameters and options
See also section T
ELEPHONE OPTIONS
p. 56.
Shown in square brackets are the names used in keypads.
Max. redial number for one round [Repetition cnt.] – the number of attempts to get through
after which the control panel will give up messaging for the current round, if it fails to
establish connection (the number is busy).
10.1.1 Telephone numbers
Description – telephone name or description (up to 16 characters).
Telephone number – the telephone number to which messaging is effected.
Type of messaging – selection of the messaging type for the given telephone number (0 –
voice; 1 – PAGER type 1; 2 – PAGER type 2; 3 – PAGER type 3).