SATEL INTEGRA Plus 59
Grade 3 – with this option enabled, the system operates as required by the EN 50131
standard for Grade 3, i.e.:
starting the arming procedure may be impossible, or, if started, the arming procedure
may fail, if some zones are violated in the partition, or there is a trouble in the system;
LCD keypads, partition keypads, proximity card arm/disarm devices and reader
expanders do not signal alarms;
the
LEDs in keypads indicate alarms only when code has been entered and
confirmed with the key;
– the blinking LED in keypads means that there is a trouble in the system, some
zones are bypassed, or there has been an alarm;
new access codes in the system must be composed of at least 6 characters (U
SER CODE
MIN
.
LENGTH
parameter);
– information on the arm status is displayed for maximum 60 seconds (N
O ARMED
INDICATION AFTER
parameter);
the following global options are enabled (cannot be disabled):
T
ROUBLE MEMORY UNTIL REVIEW
;
D
O NOT SHOW ALARM IF ARMED
;
B
LOCK KEYPAD AFTER
3
WRONG CODES
;
W
ARN WHILE ARMING IF TROUBLE
;
D
ISPLAY VIOLATED
/
BYPASSED ZONES ON ARMING
;
the following global options are disabled (cannot be enabled):
D
O NOT ARM IF TAMPERED
;
D
O NOT ARM IF BATTERY TROUBLE
;
R
EQUIRED
S
YSTEM
R
ESET AFTER VERIFIED ALARM
;
D
O NOT ARM IF TROUBLE
;
D
O NOT ARM IF OUTPUTS TROUBLE
;
D
O NOT ARM IF REPORTING TROUBLE
;
– the T
AMPER ALARM ALWAYS LOUD
option is disabled for all zones, keypad and expander
buses (the option cannot be enabled);
– the V
ALID WITHIN
30
SEC
option is enabled for all partitions (cannot be disabled);
the entry delay time (global and for individual zones) can be up to 45 seconds (if longer,
it will be automatically reduced);
– the R
EPORTING DELAY
option is enabled for the 4. P
ERIMETER
, 5. I
NSTANT
, 6. E
XIT
,
7. D
AY
/N
IGHT
and 64...79 B
YPASSING
GROUP
: 1...16 zone types (the option cannot be
disabled);
– the A
BORT DELAY
option is enabled for the 0. E
NTRY
/E
XIT
, 1. E
NTRY
, 2. D
ELAYED
,
3. I
NTERIOR DELAYED
, 85. E
NTRY
/E
XIT
CONDITIONAL
and 86. E
NTRY
/E
XIT
FINAL
zone
types (the option cannot be disabled);
– the P
RIORITY
option is enabled for the 9. 24
H
T
AMPER
zone type (the option cannot be
disabled);
– the A
UTO
-
RESET
3
and A
UTO
-
RESET
1
options are disabled for the 12. P
ANIC AUDIBLE
and
13. P
ANIC SILENT
zone types (the options cannot be enabled);
AC loss report delay (for the control panel and all modules with power supply units) can
be up to 60 minutes (if longer, it will be automatically reduced);
AC loss report delay (for the control panel and all modules with power supply units)
cannot be equal to 0 (if the value 0 is entered, 1 minute will be programmed);