Saia-Burgess Controls AG
User Manual Standby System │ Document 27-645 │ Edition ENG 02 │ 2017-04-26
Programming
Diagnostic
2-30
2
Device’s Serial Number not dened in ‘Downloader Options’
It is a good idea to check the destination PCD’s serial number, to be extra-sure
that you are downloading the program into the correct PCD, especially if it is one
of many on a network. To do this, open the device’s Downloader Options from the
-
“Hardware Information” dialog, or with S-Bug’s Display Sys-info command.
Dierent program names
name” is checked, then you will see this error if the connect PCD contains a pro-
PCD.
Failed to read program name
Caused by a communications error. The program name cannot be validated.
Invalid Primary CPU 1 IP address
Invalid Secondary CPU 1 IP address
The IP address of the Primary or Secondary CPU 1, used by each CPU 1 for
-
ration to CPU 0, which also updates CPU 1.
IP address not congured in Device Congurator
IP address not congured in PCD
Run failed
After downloading the programs to CPUs 0 and 1, the PCD is put into run with a
‘run all CPUs’ telegram. This error occurs if the command failed. This can occur
if there is a communications error of if the PCD is in HALT.
S-Bus station number not congured in Device Congurator
S-Bus station number not congured in PCD
-
Secondary CPU 0 and Secondary CPU 1 are the same device, check the On-
line Settings