Saia-Burgess Controls AG
User Manual Standby System │ Document 27-645 │ Edition ENG 02 │ 2017-04-26
Diagnostic
2-16
2
2.5.3 Creating a Default RIO Conguration
A Standby system uses the RIO type PCD3.T668. This type is automatically used
RIOs can be programmed to reduce the amount of processing done by the man-
ager device (CPU1). If programmed, they will also run autonomously if communi-
cations with the active manager device has failed.
-
template for each new RIO. See Project Manager’s help “How to create a RIO
network” for details.
2.5.4 Error and Warning Messages
The following errors may be reported in Project Manager’s “Messages” window
-
load is done. Errors should be corrected before continuing.
Error Messages
Error 7000: Primary device not found: <device_name>
Error 7000: Secondary device not found: <device_name>
The device does not exist in the project. If the name is incorrect, rename it or
create a device with the correct name and the type PCD3.M6880. To create the
OK, and answer ‘Yes’ to the “Do you want to create...” message box.
Error 7000: Redundant device not found: <device_name>
The device does not exist in the project. You cannot create a device with the
press OK, and answer ‘Yes’ to the “Do you want to create...” message box.
Error 7001: Primary device is not a PCD3.M6880
Error 7001: Secondary device is not a PCD3.M6880
Error 7001: Redundant device is not a PCD3.M6880-CPU1
wrong PCD type. If it’s the primary or secondary device, then you can use the
redundant device name and press OK to create the new device.
Error 7002: Primary device symbol le not dened: <le_path>
Error 7002: Secondary device symbol le not dened: <le_path>
Error 7002: Redundant device symbol le not dened: <le_path>
Error 7003: Primary device does not reference Redundant device’s symbol