Saia-Burgess Controls AG
User Manual Standby System Document 27-645 Edition ENG 02 2017-04-26

Diagnostic
2-17
2
le: <le_name>
Error 7003: Secondary device does not reference Redundant device’s sym-
bol le: <le_path>
Error 7004: Redundant device does not reference Primary device’s symbol
le: <le_path>
Error 7004: Redundant device does not reference Secondary device’s sym-
bol le: <le_path>

The primary and secondary devices should reference the redundant device’s
symbols (e.g. FromRedSymbols.sy5), the redundant device should reference

ToRedSymbolsSecondary.sy5)
Error 7005: Invalid or missing Primary IP address for Redundant device
Error 7005: Invalid or missing Secondary IP address for Redundant device
Error 7005: Invalid or missing Subnet Mask for Redundant device
Error 7005: Invalid or missing Default Gateway for Redundant device

correct it.
Error 7006: Primary and Secondary IP addresses for Redundant device are
the same
󰀨
dialog box and correct it.
Error 7007: Invalid ‘Online Settings’ for Redundant device (needs Sta-
tion=253, Auto Station=No): <device_name>
This is possible because the ‘Online Settings’ does not know what the device
type is, and cannot stop the user changing the settings. Open the ‘Online Set-
tings’ for the redundant device and correct them.
Error 7008: Primary device symbol le has wrong extension: <le_name>
Error 7008: Secondary device symbol le has wrong extension: <le_name>
Error 7008: Redundant device symbol le has wrong extension: <le_name>



you.
Error 7009: Primary device symbol le is not a ‘Symbols le’, see Properties:
<le_name>
Error 7009: Secondary device symbol le is not a ‘Symbols le’, see Proper-
ties: <le_name>
Error 7009: Redundant device symbol le is not a ‘Symbols le’, see Proper-
ties: <le_name>


Error 7011: Redundant device’s S-Bus station number must be 253
The S-Bus station number for the Redundant device (CPU1) must be 253. This