Saia-Burgess Controls AG
User Manual Standby System Document 27-645 Edition ENG 02 2017-04-26

Diagnostic
2-18
2

number is 253.
Error 7012: Primary and Secondary devices have the same S-Bus station
number
󰀨-
bers. You will see this error if a new project has been created and the station
numbers have not yet been assigned (both are 0).
Warning Messages
Warning 7101: Invalid ‘Channel Type’ in Online Settings, use S-Bus, S-Bus
USB or SOCKET
Only these channels can be used to communicate with a standby controller.
Warning 7102: Invalid ‘S-Bus Station Number in Online Settings (is n, should
be n)
The S-Bus station number on the Online Settings does not match the S-Bus

Warning 7103: Invalid ‘IP Address’ in Online Settings (is xxx.xxx.xxx.xxx,
should be xxx.xxx.xxx.xxx)
The IP address in the Online Settings does not match the IP address in the

Warning 7104: Invalid Online Settings, ‘PGU Mode’ should be ‘No’
PGU mode cannot be used to communicate with a standby controller. It may
cause connection to the wrong device or CPU. Open the Online Settings and
ensure ‘PGU’ mode is ‘No’.
Warning 7105: Invalid Online Settings, ‘Auto Station’ should be ‘No’
Automatic station number detection mode cannot be used to communicate
with a standby controller. It may cause connection to the wrong device or CPU.
Open the Online Settings and ensure ‘Auto Station’ is ‘No’.