User Manual Standby System Document 27-645 Edition ENG 02 2017-04-26
Ether-SIO Diagnostics Extension
Technical Imformation
3-4
3
3.5 Ether-SIO Diagnostics Extension

two managers. These symbols are shown on the “All Publics” tab of the RIO pro-
gram’s Symbol Editor, in the group RIO:
O󰀨set System Symbol Name Values
0
RIO.GlobalDiagnostic


1
RIO.TelegramLost
0 = no telegrams lost
1 = one or more telegrams lost
2
RIO.SendError
0 = no error
1 = failed to send, or out of resources*
3
-
Reserved
4
-
Reserved
5
RIO.ActiveManager
0 = Primary
1 = Secondary
6
RIO.SecondaryManager-
NotPresent
0 = present
1 = not present
7
RIO.PrimaryManager-
NotPresent
0 = present
1 = not present