Watch Dog The TA device limits a call for max. 3 minutes. Afterwards the connection will be
interrupted.
The command below restarts the timer for next 3 minutes w/o interruption of the
communication.
It can be used with each connection independent of alarm- back- or configuration call.
2)
If the alarm device answers with #99# then the TA device did not get the DTMF
commands right. Try again to send the command.
Automatic Periodical
Call Procedure
2)
If the alarm device answers with #99# then the TA device did not get the DTMF
commands right. Try again to send the command.
Rescue Service Handling from → to Remote Alarm Device
Watch Dog
- start the watch
dog with
#23# → - The TA device starts
the timer for next 3
minutes
←
#00#
2)
- sends ok
Rescue Service Handling from → to Remote Alarm Device
Establish
Connectio
n
← ring - The TA device dials
the rescue alarm
number
- the rescue service
answers the incoming
call
Verify
Installation
ID
- ask the Installation ID
with
#10# →
←
#12xxxxxxxxxxxx#
- sends Installation ID
(x=0 ... 999999999999)
Verify Unit
ID
- ask the Unit ID with #13# →
←
#14abcd# - sends Unit ID
(a=1 ... 8)
(b=1: test call)
Set Line
Test Timer
- Set line test timer
(x=0 ... 99999 minutes)
#74xxxxx#→ - sets line test timer
←
#00#
2)
- sends ok
Close
Connectio
n
- send the hang up
signal
#24# →
- the rescue service
hangs up
←
#00#
2)
- sends ok
TA device hangs up the
phone line