EasyManua.ls Logo

Schindler 6300 - Page 98

Schindler 6300
269 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Schindler 3100/3300/6300 J 43402603 / 01 98/269
Copyright © 2017 INVENTIO AG
Step 2: LOP counting [LC _ _ ]
LOP counting should start automatically after each LOP addressing in CF00 or after
some configuration changes (CF40 or CF 60-80) on a BIO bus node. If it does not
start automatically, it must be started manually.
Manual LOP counting must also be performed after replacing the microprocessor
PCB. To manually do the LOP count via COP, select CF 00, press DTO, press 0 and
DTO again. The COP shows “LC” during the LOP count.
[25822; 13.02.2008]
7 Press the DT-O to confirm the correct configuration of the just configured LOP.
The COP answers with a beep.
The CPID shows “LE” again.
The ACID shows next floor up.
8 Repeat the LOP configuration steps for each floor and each door side.
9 When all floors are configured, disable the configuration mode.
This starts the LOP counting automatically.
No User Interaction HMI
1
Enter configuration mode menu 40.
2 Choose CF00 and confirm with “OK”. LE - -
3 Change with the UP/DOWN button to [LE 00] LE 00
4 Press "OK".
LOP counting is indicated by blinking [LC_ _ _ _]. This can
take up to several minutes.
LC _ _ _ _
5 After LOP counting is finished leave configuration mode by
pressing “ESC” and by deactivating menu 40.
(Change [40_ _ _1] to [40_ _ _0] and press “OK”)
40 1
40 0
40
No Step

Table of Contents

Related product manuals