GC1100 SEDEMAC
Page | 25
Level 0
Level 1 (On
screen)
Level 2 (On screen) *
Parameters (On screen)
(WARNING THRESHOLD)
(LOP) Circuit Fault Action
(OPEN CKT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
(LOP) Lube Oil Pressure Sensor
Calibration Table
Refer Table 25
Outputs
(OUTPUTS)
Output X
(OUT X)
X= A/B/C/D/E/F
Source
(SOURCE)
Refer Table 26
On Activation
(ON ACTIVATION)
Energise/De – energise
Timers
(TIMERS)
Cranking
(CRANKING
TIMER)
Crank Hold Time
(CRANK HOLD TIME)
1 15 sec
Crank Rest Time
(CRANK REST TIME)
2 60 sec
Manual Start Delay
(MANUAL START DELAY)
0 30 sec
Auto Start Delay
(AUTO START DELAY)
0 – 43200 sec
General
(GENERAL
TIMER)
Safety Monitoring Delay
(SAFETY MONITOR DELAY)
10 60 sec
Mains Detect Delay
(MAINS DETECT DELAY)
1 300 sec
Alternator Detect Delay
(ALT DETECT DELAY)
1 30 sec
Warm Up Delay
(WARM UP DELAY)
0 60 sec
Return To Mains Delay
(RETN-TO-MAINS DELAY)
0 600 sec
Engine Cooling Time
(ENG COOL TIME)
0 300 sec
Stop Action Time
(STOP ACTION TIME)
10 120 sec
Additional Stopping Time
(ADDN STOPPING TIME)
0 120 sec
Load Transfer Delay
(LOAD TRANSFER DELAY)
0 60 sec
Power Save Mode Delay
(PWR SAVE MODE DELAY)
5 1800 sec
Screen Changeover Time
(SCRN CHNGOVER TIME)
1 1800 sec
Deep Sleep Mode Delay
(DEEP SLP MODE DELAY)
5 1800 sec
Sounder Alarm Time
(SOUNDER ALARM TIMER)
1 300 sec
Auto Exit Config Mode
(AUTO EXIT TIMER)
10 – 1800 sec