SEDEMAC GC1100 - Generator Configuration and Monitoring

SEDEMAC GC1100
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GC1100 SEDEMAC
Page | 26
Level 0
Level 1 (On
screen)
Level 2 (On screen) *
Parameters (On screen)
Generator
(GENERATOR)
Alternator
Configuration
(ALT CONFIG)
Alternator Present
(ALT PRESENT)
No/Yes
Number of Poles
(NUMBER OF POLES)
2/4/6/8
AC System
(ALT AC SYSTEM)
1 Phase/3 Phase
Min Healthy Voltage
(MIN HEALTHY VOLT)
50 350 Volt Ph-N
Min Healthy Frequency
(MIN HEALTHY FREQ)
10 75 Hz
Phase Reversal Detection
(PHASE REVERSE DETECT)
Disable/Enable
Phase Reversal Action
(PHASE REVERSE ACTION)
None/Notification/Warning
/Electrical Trip/Shutdown
Auto Load Transfer
(AUTO LOAD TRANSFER)
Disable/Enable
Voltage
Monitoring
(VOLT
MONITOR)
Under-voltage Shutdown
(UNDER VOLT SHUTDOWN)
Disable/Enable
Under-voltage Shutdown
Threshold
(UV SHUTDWN THRESHLD)
50 295 V Ph-N
Under-voltage Warning
(UNDER VOLT WARNING)
Disable/Enable
Under-voltage Warning
Threshold
(UV WARNING THRESHOLD)
55 300 V Ph-N
Over-voltage Shutdown
(OVER VOLT SHUTDOWN)
Disable/Enable
Over-voltage Shutdown
Threshold
(OV SHUTDWN THRESHLD)
105 – 350 V Ph-N
Over-voltage Warning
(OVER VOLT WARNING)
Disable/Enable
Over-voltage Warning Threshold
(OV WARNING THRESHOLD)
100 – 345 V Ph-N
Frequency
Monitoring
(FREQ
MONITOR)
Under-frequency Shutdown
(UNDER FREQ SHUTDOWN)
Disable/Enable
Under-frequency Shutdown
Threshold
(UF SHUTDWN THRESHLD)
10.0 – 59.0 Hz
Under-frequency Warning
(UNDER FREQ WARNING)
Disable/Enable
Under-frequency Warning
Threshold
(UF WARNING THRESHOLD)
11.0 – 60.0 Hz