EasyManuals Logo

SEDEMAC GC1100 User Manual

SEDEMAC GC1100
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
GC1100 SEDEMAC
Page | 28
Level 0
Level 1 (On
screen)
Level 2 (On screen) *
Parameters (On screen)
(PHASE REVERSE DETECT)
Phase Reversal Action
(PHASE REVERSE ACTION)
None/Notification
Partial Healthy Detection
(PARTL HLTHY DETECT)
Disable/Enable
Under-voltage
Monitoring
(UNDER VOLT
MON)
Enable
(ENABLE)
No/Yes
Trip
(TRIP)
50 298 V Ph-N
Return
(RETURN)
52 300 V Ph-N
Over-voltage
Monitoring
(OVER VOLT
MON)
Enable
(ENABLE)
No/Yes
Trip
(TRIP)
102 – 350 V Ph-N
Return
(RETURN)
100 – 348 V Ph-N
Under-
frequency
Monitoring
(UNDER FREQ
MON)
Enable
(ENABLE)
No/Yes
Trip
(TRIP)
10.0 – 59.0 Hz
Return
(RETURN)
11.0 – 60.0 Hz
Over-frequency
Monitoring
(OVER FREQ
MON)
Enable
(ENABLE)
No/Yes
Trip
(TRIP)
26.0 – 75.0 Hz
Return
(RETURN)
25.0 – 74.0 Hz
Engine
(ENGINE)
Crank
Disconnect
(CRANK
DISCON)
Start Attempts
(START ATTEMPTS)
1 – 9
Disconnect On Oil Pressure
Sensor
(DISCONN ON LOP SENS)
Disable/Enable
Pressure Sensor Monitoring
Threshold
(DISCONN LOP THRESH)
0.5 – 10.0 bar
Monitor Pressure Switch Before
Crank
(MON LLOP BEFR CRANK)
Disable/Enable
Monitor Pressure Sensor Before
Crank
(MON LOP BEFR CRANK)
Disable/Enable
Disconnect On Oil Pressure
Switch
Disable/Enable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SEDEMAC GC1100 and is the answer not in the manual?

SEDEMAC GC1100 Specifications

General IconGeneral
BrandSEDEMAC
ModelGC1100
CategoryController
LanguageEnglish

Related product manuals