GC1100 SEDEMAC
Page | 39
Sr.
No.
Alarms
Causes
Action options
Notification
6
Low Water Level
Switch
Indicates that radiator water level is below the pre-set
threshold
Shutdown/
Warning/
Electrical trip/
Notification
7
Auxiliary
Input/user
defined name
Configured auxiliary input has triggered longer than pre-
set duration
Shutdown/
Warning/
Electrical trip/
Notification
8
Anlg LOP Ckt
Open
The oil pressure sensor is detected as not being present
Shutdown/
Warning/
Electrical trip/
Notification
9
Engine Temp Ckt
Open
The temperature sensor is detected as not being present
Shutdown/
Warning/
Electrical trip/
Notification
10
Fuel Level Ckt
Open
The fuel level sensor is detected as not being present
Shutdown/
Warning/
Electrical trip/
Notification
11
Fuel Theft
The fuel consumption has exceeded the pre-set
threshold
Warning
12
Emergency Stop
Configured as digital input has triggered longer than pre-
set duration or when the immediate shutdown is required
Shutdown
13
Fail To Stop
Indicates that genset has not stopped after sending Stop
command
Shutdown
14
Fail To Start
Indicates that genset has not started after the pre-set
number of Start attempts
Shutdown
15
R Phase Over
Voltage
Indicates that genset L1(R) Phase voltage has exceeded
the pre-set over voltage threshold.
Shutdown/
Warning
16
Y Phase Over
Voltage
Indicates that genset L2(Y) Phase voltage has exceeded
the pre-set over voltage threshold
Shutdown/
Warning
17
B Phase Over
Voltage
Indicates that genset L3(B) Phase voltage has exceeded
the pre-set over voltage threshold
Shutdown/
Warning
18
R Phase Under
Voltage
Indicates that genset L1(R) Phase voltage has fallen
below pre-set under voltage threshold.
Shutdown/
Warning
19
Y Phase Under
Voltage
Indicates that genset L2(Y) Phase voltage has fallen
below pre-set under voltage threshold
Shutdown/
Warning
20
B Phase Under
Voltage
Indicates that geset L3(B) Phase voltage has fallen
below pre-set under voltage threshold
Shutdown/
Warning
21
DG Phase
Reversal
Alternator phase sequence (R-Y-B) is not correct
Shutdown/
Warning/
Electrical trip/
Notification