9.19 ExP[2] – External Protection - Module
9.19.1
ExP[2]: Device Planning Parameters
ExP[2] . Mode [Device planning / Projected Elements]
use “-”, use
╚═▷ Device planning
P.1
External Protection - Module, general operation mode
ExP[2] . De󰈛nition [Device planning / De󰊟nition]
Trip Trip, Alarm
╚═▷ De󰊟nition
P.1
External Protection - Module: If set to “Alarm”: The function operates as a supervision function, i.e. a fault generates
neither alarm nor trip, but an »Alarm« signal gets issued instead. If set to “Trip”: The function operates as a
protection function, i.e. trips the breaker in case of a fault.
9.19.2
ExP[2]: Settings
ExP[2] . Function [Protection Para / ExP[2]]
Active Inactive, Active
╚═▷ Mode
P.1
Permanent activation or deactivation of module/stage.
ExP[2] . t [Protection Para / ExP[2]]
0.00s 0.00s  . . .  60.00s P.1
Time delay for trip or alarm
ExP[2] . Trigger Signal [Protection Para / ExP[2]]
If: Device Variant/Inputs = Without Inputs
“-”
“-”
“-”
“-”
“-”
“-”, Prot . DI 1, Prot . DI 2
“-”
If: Device Variant/Inputs = Without Inputs
“-”
“-”
P.1
105WIC1WIC1-2.0-EN-REF