ThR . τ-warm [Protection Para / ThR]
300s 10s . . . 30000s P.1
Warming-up time constant
ThR . τ-cool [Protection Para / ThR]
300s 10s . . . 30000s P.1
Cooling time constant
ThR . Initial Thermal Level [Protection Para / ThR]
Zero Zero, Last Stored Value
╚═▷ Initial Thermal Level
P.1
Select the criterion for setting the initial thermal level after a restart of the device.
ThR . ExBlo [Protection Para / ThR]
“-” “-” . . . Prot . Pos OFF
╚═▷
P.1
External blocking of the module if the state of the assigned signal is true.
9.15.3
ThR: Direct Controls
ThR . Rst. Thermal Lev. [Operation / Reset]
Inactive Inactive, Active
╚═▷ Mode
P.1
Reset the thermal level
9.15.4
ThR: Input States
ThR . ExBlo-I [Operation / Status Display / ThR]
Module input state: External blocking
9.15.5
ThR: Signals (Output States)
ThR . Active [Operation / Status Display / All Actives]
[Operation / Status Display / ThR]
Signal: active
94 WIC1 WIC1-2.0-EN-REF
9 Protection Parameter
9.15.3 ThR: Direct Controls