9.9 I>> – Phase Overcurrent Stage
9.9.1
I>>: Device Planning Parameters
I>> . Mode [Device planning / Projected Elements]
use “-”, use
╚═▷ Device planning
P.1
Phase Overcurrent Stage, general operation mode
I>> . Denition [Device planning / Denition]
Trip Trip, Alarm
╚═▷ Denition
P.1
Phase Overcurrent Stage: If set to “Alarm”: The function operates as a supervision function, i.e. a fault generates
neither alarm nor trip, but an »Alarm« signal gets issued instead. If set to “Trip”: The function operates as a
protection function, i.e. trips the breaker in case of a fault.
9.9.2
I>>: Settings
I>> . Function [Protection Para / I>>]
Active Inactive, Active
╚═▷ Mode
P.1
Permanent activation or deactivation of module/stage.
57WIC1WIC1-2.0-EN-REF
9 Protection Parameter
9.9 I>> – Phase Overcurrent Stage