EasyManuals Logo

Seg WIC1 Reference Manual

Seg WIC1
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #116 background imageLoading...
Page #116 background image
BkrWear . Ir [Protection Para / Condition Monitoring / BkrWear]
16.0A
Only available if:
BkrWear . Mode = Counters, Wear Lev.
5.6A  . . .  10000.0A P.1
Rated current of the circuit breaker
BkrWear . N(Ir) [Protection Para / Condition Monitoring / BkrWear]
100
Only available if:
BkrWear . Mode = Counters, Wear Lev.
2  . . .  100000 P.1
Number of switching operations at the rated current of the circuit breaker
BkrWear . Isc [Protection Para / Condition Monitoring / BkrWear]
1120.0A
Only available if:
BkrWear . Mode = Counters, Wear Lev.
16.0A  . . .  100000.0A P.1
Maximum short-circuit current of the circuit breaker
BkrWear . N(Isc) [Protection Para / Condition Monitoring / BkrWear]
10
Only available if:
BkrWear . Mode = Counters, Wear Lev.
1  . . .  50000 P.1
Number of switching operations at the maximum short-circuit current of the circuit breaker
9.22.2.3 BkrWear: Direct Controls
BkrWear . Reset [Operation / Reset]
False False, True
╚═▷ True or not true
P.1
Direct Command to reset the counters and the wear level of the circuit breaker.
9.22.2.4 BkrWear: Signals (Output States)
BkrWear . Active [Operation / Status Display / All Actives]
[Operation / Status Display / BkrWear]
Signal: active
116 WIC1 WIC1-2.0-EN-REF
9 Protection Parameter
9.22.2.3 BkrWear: Direct Controls

Table of Contents