15 Parameterisation
59
Both parameters can be set independently.
dtyp inverts the function of the switching output.
If the value is NO, the switching output will work as normally open
(NO) contact; if the value is NC, the switching output will work as
normally closed (NC) contact.
ddly delays the reaction of the switching output by up to 200.0s.
This value holds true for switching on and switching off.
15.4 Display
The STS sensor is equipped with a removable display. The
sensor can be parameterised using the display (optionally
using the PC).
Even without the display, the sensor works as previously
parameterised.
Dsp defines the display value. The display can show the
opacity/absorption, the temperature in °C, or both values in an
alternating fashion.
15.5 Keylock
You can protect the keyboard against unauthorised
access.
Aulo activates the keylock by setting a value of more than “0”.
The set value corresponds to the time in minutes, as of which the
keyboard will be locked after the last entry was made. If another
entry is made, the time will start anew. If “0” is entered, the
keylock will be deactivated.
The locked keyboard can be unlocked by de-energising the sensor
for a short period of time. For this, disconnect the connector for a
short period of time and reconnect it afterwards.