MT4412E Rev.3 15/10/2019 Page 12 of 30
Dip-switch 1: Baud Rate Bus RS485
Detector and module compatibility
Smart “S” gas detectors; ST.G/IN8-S and
ST.G/OUT16-S modules
Smart “3G” gas detectors; ST.G/IN8-S and
ST.G/OUT16-S modules
Dip-switches 2 and 3: RS485 bus communication protocol
Detector and module
compatibility
Smart “S” gas detectors;
ST.G/IN8-S and ST.G/OUT16-
S modules
Smart "G" gas detectors;
STG/IN8-S and STG/OUT16-S
modules
Baud rate 9600 (if they are
not connected to the Smart
"G" bus detectors, 115200
Bps can be set (switch 1)
Dip-switches 4 and 5: Communication (baud rate) of the RS232 serial port with
the PC
115200 Bit/sec. (default)
Dip-switches 6 and 7: not used
Dip-switch 8: restore default settings
If set to ON, default data is restored when the central unit is switched on
2.2) Field device connections
The unit has 1 RS485 data bus to which 8 gas detectors can be connected
The gas detectors are connected through the serial bus (directly in the serial RS485 if equipped
with serial output or through 1 module with 8 STG/IN8 S inputs if of type 4-20 mA) and the
ST.G/OUT16-S output module
The maximum length of each serial data bus is 800 m.
To connect devices, 4 conductors are required (intended both as detectors with a serial output as
well as IN and OUT modules): 2 for the RS485 serial bus and two for powering the devices. For
this reason, two different wires must be used or a single wire that has suitable characteristics, as
described below.